Substation Automation
Devices installed for the purpose of power facility and disaster preventive and security facility in the substation(KEPCO)
Apply monitoring/measurement/control/interlock function
Automatic frequent monitoring, breakdown recording, and breakdown analyzing function
Protect short circuit and earth fault over-current and monitor load imbalance
Division | Item | Specification |
---|---|---|
Terms of use | Ambient temperature | -25¡É ~ +55¡É |
Relative humidity | 10% ~ 100% | |
Elevation | 1,500m less than | |
Rated | Frequency | 60Hz |
Voltage | Phase voltage : 110/¡î3V, Interlinear voltage : 110V | |
Electric current | 5A | |
Power | DC 125V(90~140V) | |
Outward form | Size | 445 x 255 x 247mm (W x H x D) | Form | Stand-Alone Type |
Weight | 11kg less than | |
Quality of the material | Aluminum |
Division | Specification | Note | |
---|---|---|---|
Communication port | Ethernet | 100Base-FX, 2 channels | IEC 61850 |
100Base-T, 1 channels | TCP/IP | ||
Time sync. | IRIG-B 120 or SNTP | ||
RS-232 | Serial 9pin (Female-Type), 1 port | Console | |
Serial 9pin (Male-Type), 1 port | Development purposes | ||
Enter Contact | 64 points | ||
Contact output | 28 points | ||
CT | 4 channels | ||
PT | 5 channels | ||
AI | Transducer | 10 channels | |
RTD | 4 channels | ||
Display | TFT Color Graphic LCD 7" (800 x 480) | ||
Button | 18 | ||
LED | 36 |