Substation Automation
Controlling and interlocking for field equipments such as circuit breakers and
disconnecting switchgears
Applied for 170kV GIS PT & ES bay
Programming trip and control logics
Editing the single line diagram on the dedicated PC S/W
Saving the events in 1ms resolution
Recording fault waveforms in IEEE C37.111 COMTRADE format
Self-monitoring on a regular basis
Division | Item | Specification |
---|---|---|
Terms of use | Ambient temperature | -25¡É ~ +55¡É |
Relative humidity | 10% ~ 100% | |
Elevation | 1,500m less than | |
Rated | Frequency | 60Hz |
Voltage | Phase voltage : 110/¡î3V, Interlinear voltage : 110V | |
Power | DC 125V(90~140V) | |
Outward form | Size | 445 x 255 x 247mm (W x H x D) | Form | Stand-Alone Type |
Weight | 9.5kg less than | |
Quality of the material | Aluminum |
Division | Specification | Note | |
---|---|---|---|
Communication port | Ethernet | 100Base-FX, 2 channels | IEC 61850 |
100Base-T, 1 channels | TCP/IP | ||
USB | B-Type 1 channels | Wired-X | |
Time sync. | IRIG-B 120 or SNTP | ||
RS-232 | D-SUB 9pin (Male-Type), 1 port | Development purposes | |
Enter Contact | 64 points | ||
Contact output | 28 points | ||
PT | 8 channels | ||
AI | 2 channels | ||
Display | TFT Color Graphic LCD 7" (800 x 480) | ||
Button | 18 | ||
LED | 26 |