Transformer current differential motion protecting function
Support high speed current differential motion protection (87-HOC) or current proportion differential motion protection (87R) in the use of current difference between phases of transformer
Calculate phasor on current of transformer and also the current difference between phases of transformer
Use the second harmonic wave and support malfunction preventing function from magnetizing inrush current
Lock the operation of protective relay and prevent alarm or malfunction according to the results of real-time monitoring on protective relay
Over-current protecting function
Frequent (50) or one-time (51, including definite time operation) over-current protecting function on 3 phases current and N-phase current on each high pressure and low pressure in the transformer
Support OLTC Blocking (50B) function
Support blocking (50B) function on impact pressure relay
Support various standard inverse time operation characteristics curve
Lock the protective relay and prevent alarm or malfunction according to the results of frequent monitoring on protective relay
General Specification
Division
Item
Specification
Note
Terms of use
Ambient temperature
-25¡É ~ +55¡É
Relative humidity
10% ~ 90%
Elevation
1,500m
less than
Rated
Frequency
60Hz
Electric current
5A
Voltage
110/¡î3 V
Power
DC 125V (90~140V)
Auxiliary power source
Single phase 220V
Outward form
Size
318 x 261 x 270mm (W x H x D)
Form
Stand-Alone Type
Weight
7.5kg
less than
Quality of the material
Aluminum
Hardware Specification
Division
Specification
Note
Communication port
Ethernet
100Base-FX, 2 channels connector : ST type, Multi-mode, 1310nm