Substation Automation
IED to be installed in field control panel of main 154kV transformer
Use as control IED to protect main transformer and monitoring (control) IED for each bank
Provide monitoring and control input/output contact point on OLTC or cooling device
Apply monitoring/measurement/control/interlock function
Apply 7-inch TFT LCD equipped with touch screen
Division | Item | Specification |
---|---|---|
Terms of use | Ambient temperature | -25¡É ~ +55¡É |
Relative humidity | 10% ~ 100% | |
Elevation | 1,500m less than | |
Rated | Frequency | 60Hz |
Voltage | Phase voltage : 110/¡î3V, Interlinear voltage : 110V | |
Electric current | 5A | |
Power | DC 125V(90~140V) | |
Outward form | Size | 445 x 255 x 247mm (W x H x D) | Form | Stand-Alone Type |
Weight | 9.5kg less than | |
Quality of the material | Aluminum |
Division | Specification | Note | |
---|---|---|---|
Communication port | Ethernet | 100Base-FX, 2 channels | IEC 61850 |
100Base-T, 1 channels | TCP/IP | ||
RS-232 | Serial 9pin (Male-Type), 2 port | Operational Software , Reserve | |
Time sync. | IRIG-B 120 or SNTP | ||
Enter Contact | 48 points | ||
Contact output | 28 points | ||
CT | 4 channels | ||
PT | 5 channels | ||
AI | 4~20mA DC : 10
channels
RTD : 12 channels |
||
Display | TFT Color Graphic LCD 7" (800 x 480) | ||
Button | 18 | ||
LED | 42 |